In stock 10 available
The Moeller NZM7-100S-M is a molded case circuit breaker designed for medium-duty industrial applications. It ensures protection of circuits from overloads and short circuits, while the U-NZM7 undervoltage trip module provides added safety by tripping the breaker when control voltage falls below a safe threshold. Breaker Unit: NZM7-100S-M Rated Operational Voltage (Ue): Up to 690V AC (50/60Hz) Rated Insulation Voltage (Ui): 800V Rated Impulse Withstand Voltage (Uimp): 8 kV Rated Current (In): 100 A Interrupting Capacity (Icu): 65 kA at 400V AC 36 kA at 690V AC Number of Poles: 3P Tripping Characteristics: Adjustable thermal and magnetic trip units Mounting: Fixed, panel mount Standard Compliance: IEC/EN 60947-2 Undervoltage Trip Unit: U-NZM7 (24VDC) Rated Voltage: 24V DC Operating Range: Typically 70–110% of rated voltage Trip Threshold: Triggers breaker if voltage drops below ~70% of nominal Power Consumption: ~3 W Installation: Plug-in accessory to the main NZM7 breaker body Function: Prevents automatic restart after power failure or undervoltage condition Additional Specifications: Ambient Operating Temperature: -25°C to +55°C Dimensions (NZM7 Body Approx.): H 250 mm × W 105 mm × D 100 mm Weight: ~4.5 kg with accessories
Condition: Used
Weight: 7.00
Depth: 8.00
Length: 8.00
Width: 8.00
SKU: 42626 4.S5.11.4