This is a manual motor protector designed to provide motor circuit protection through thermal and magnetic trip mechanisms. It offers adjustable current settings and includes built-in START/STOP control. Model: 140-MN-0160 Series: C Rated Operational Voltage: Up to 600 VAC (3-phase) Rated Current: 2.5 A max Current Adjustment Range: 1.0 – 1.6 A (adjustable via front dial) Trip Class: Manual reset, 120% FLA tripping Interrupt Rating: – 100 kA @ 400 V (with proper backup fuse) – UL/CSA: 480Y/277 VAC, 5 kA Motor Ratings (3-phase): – 0.1 HP @ 115 V – 0.5 HP @ 200–240 V – 1.0 HP @ 480 V – 1.5 HP @ 575 V Contacts: Built-in STOP/RESET (red) and START (green) pushbuttons Auxiliary Contact Ratings: – B300 (AC) – R300 (DC) Wire Range: #18 to #10 AWG (Cu only) Mounting: DIN rail or panel Certifications: UL Listed, CSA, CE Country of Origin: Switzerland Please review pictures carefully and let us know if you have any questions!